| Name | Type, range | SUBID | Default | Description |
|---|---|---|---|---|
| cfg | string | 98 | 9600/8N1 | cfg='SPEED/BPS', where |
| • SPEED – baud rate [1200..115200]; | ||||
| • B – data length [7,8]; | ||||
| • P – presence and type of parity bit [N(No parity),E(Even parity),O(Odd parity)]; | ||||
| • S – stop bit length [1, 1.5 or 2]. | ||||
| Example: |
hw="cfg='9600/8N1'" |
| [Protocol] | string | 98 | — | Protocol setting is described by protocol parameter. The following protocols are supported:
• 'modbus', Modbus protocol, at the end of redirection the checksum CRC16(Modbus) is added;
• 'dmx', DMX protocol;
• 'CO2' for connecting Larnitech CO2 sensors;
• 'salda' for connecting Salda ventilation.
Example:
hw="cfg='9600/8N1' modbus" |
| echo | on; off | 98 | 'off' | For settings check out and testing echo parameter can be used. Moduleecho-reply can be turned on or off with the help of this parameter. Echo parameter value:
• 'off'
• 'on'
Example:
hw="cfg='9600/8N1' echo='off'" |